Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 390R — Steam Gauges
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 390P, 390Q. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 390 p
Reg. 390 q
Reg. 390 r
|
Earlier text: the 2008 DIPP web edition
Steam Gauges
The steam gauges on all boilers shall be removed and the Inspector shall test them and compare their readings with a standard test gauge. The readings of the steam gauges shall be observed and compared when making an inspection with steam on the boiler, where several boilers are in service connected to a common steam main. The location of the steam gauges shall be noted to see whether or not it is exposed to high temperature either externally, as would be the case if placed close to the smoke flue or other high heated part of the boiler or setting, or exposed to heat internally due to lack of protection of the gauge spring with a proper syphon or trap to prevent steam from coming in contact with the spring. The Inspector shall see that provisions are made for blowing out the pipe leading to the steam gauge.