Safety Valves
As the safety valves are the most important attachments on the boiler, they shall be inspected with the utmost caution. There should be no accumulations of rust, scale, or other foreign substances located in the casings so as to interfere with the free operation of the valves. The setting and freedom of the safety valves should be tested preferably by raising the steam pressure to the blow-in-off point, or if this cannot be done, the valves shall be tested by means of the try levers to ascertain if they are free. Where the steam discharged from a safety valve is led through a pipe the Inspector shall determine at the time the valve is operating whether or not the drain, opening in the discharge pipe is free and in accordance with the Regulations.
If the Inspector deems it necessary, in order to determine the freedom of discharge from a safety valve, the discharge connections should be removed. Under no circumstances should a stop valve be permitted between a boiler and its safety valve.