Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 390N — Baffling-Water tube boilers
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 390M, 390O. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 390 m
Reg. 390 n
Reg. 390 o
|
Earlier text: the 2008 DIPP web edition
Baffling-Water tube boilers
In water-tube boilers, it should be noted, as far as possible, whether or not the proper baffling is in place. In many types of boilers the absence of baffling often causes high temperatures on portions of the boiler structure which are not intended to be exposed to such temperatures, from which a dangerous condition may result. The location of combustion arches with respect to tube surfaces shall be carefully noted. These are sometimes arranged so as to cause the flame to impinge on a particular part of a boiler and produces overheating of the material and consequent danger of the rupture of the part.