Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 390M — Water column
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 390N, 390O. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 390 m
Reg. 390 n
Reg. 390 o
|
Earlier text: the 2008 DIPP web edition
Water column
The piping to the water column shall be carefully noted to see that there is no chance of water being pocketed in the piping forming the steam connection to the water column. The steam-pipe should preferably drain towards to the water column. The water pipe connection to the water column must drain towards the boiler.
The relative position of the water column to the fire surfaces of the boiler shall be observed to determine whether the column is placed in accordance with the Regulations. The attachments shall be examined to determine their operating condition.