BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)

Regulation 390E — Manholes and other Openings

Unofficial DPIIT web edition · not verified0 amendments found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 390D, 390F. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette

Reg. 390 d

Stays

All stays, whether diagonal or through, shall be examined to note that they are in even tension. All fastened ends shall be examined to note whether cracks exist where the stays are punched or drilled for rivets or bolts and, if not found in proper tension, the Inspector should recommended their proper adjustment.


Reg. 390 e

Manholes and other Openings

The manhole and other reinforcing plates, as well as nozzles or other connections flanged or screwed into a boiler, shall be examined internally as well as externally to see that they are not cracked or deformed, and wherever possible observation shall be made from the inside of the boiler, as to the thoroughness with which its pipe connections are made to the boiler. All openings to external attach-pipe connections are made to the boiler. All openings to external attachments, such as water column connections, openings in dry pipes and openings to safety valves, shall be noted to see that they are free from obstructions.


Reg. 390 f

Fire Surfaces.-Bulging, Blistering, Leaks

Particular attention shall to given to the plate or tube surface exposed to the fire. The Inspector shall observe whether any part of the boiler has become deformed during operation by bulging or blistering; the former is a distortion of the entire thickness of the plate or tube where it takes place, while the latter is a lamination or separation of the plate due to foreign material being embedded in the ingot before the plate is rolled. If bulges or blisters are of such size as would seriously weaken the plate or tube and especially when the leakage is noted coming from those defects, the boiler shall be discontinued from service until the defective part or parts have received proper repairs. Careful observation shall be made to defect leakage from any portion of the boiler structures, particularly in the vicinity of seams and tube ends. Fire tubes sometimes blister but rarely collapse; the Inspector should look through the tubes for such defects and if they are found with a sufficient degree of distortion they should be removed.
Earlier text: the 2008 DIPP web edition

Manholes and other Openings

The manhole and other reinforcing plates, as well as nozzles or other connections flanged or screwed into a boiler, shall be examined internally as well as externally to see that they are not cracked or deformed, and wherever possible observation shall be made from the inside of the boiler, as to the thoroughness with which its pipe connections are made to the boiler. All openings to external attach-pipe connections are made to the boiler. All openings to external attachments, such as water column connections, openings in dry pipes and openings to safety valves, shall be noted to see that they are free from obstructions.