Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 376 — Preparation for Inspection
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 375. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 375, Reg. 376 Reg. 375* REGULATIONS FOR THE REGISTRATION OF BOILERS AND INSPECTION OF BOILERS AND STEAM-PIPES
Reg. 376 Preparation for Inspection
| |||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Preparation for Inspection
a)At every examination of boiler or the grant of renewal of a certificate, the boiler shall be empty and thoroughly clean in all its parts. Except as provided as for in subregulation (f) all doors of manholes, handholes and sightholes and cleaning plugs and all caps in the leaders and mud drums of water tube boilers, all firebars, bearers, front plates, bridge plates, fire bridges brick arches, oil fuel burners and mechanical stoker fittings shall be removed. All valves and cocks comprising the boiler mounting shall be opened up and taken apart and the valves or cocks ground, when necessary, before the Inspectors’ visit.
b)Provision shall if, required by the Inspector, be made for the removal of lagging or brick-work or other concealing part and for the drilling of plates, and for verifying the pressure gauge and safety valve dimensions and weights.
c)All smoke tubes, exterior of water tubes, smoke boxes, and external flues shall be swept clean.
d)Provision shall be made for the effective disconnection of all steam and hot water communication with another boiler under steam as required in Chapter IX-A of these Regulations
e)No blank flange/plug shall be inserted between a safety valve chest and the boiler generally and where it is permitted by the Inspector, the blank flange/plug shall be removed in his presence.
f)At alternative annual inspections and subject to a minimum of three bottom rows or all tubes subject to the first pass of heat being opened up for inspection the Inspector may at his discretion relax the preparation for inspection called for under (a) above in favour of boilers having an evaporative capacity of 200,000 lbs. per hour and over, and fed either water treated to the satisfaction of the Inspectors.
g)In the case of forced flow and forced circulation types of boilers, provisions shall be made for checking that proper circulation is maintained through all sections of the circuit by the flow of water.
* Note:- In accordance with section 7 and 8 of the Act, Inspectors are required to measure and examine boilers for registration, to examine boilers for renewal certificates, to determine subject to the approval of the Chief Inspector, the pressure at which they may be allowed to work, to grant certificate therefor and generally to convey to the owners such orders as the Chief Inspector may issue.
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 1994-11-23 | G.S.R. 607 OCR of scan | (e) | Substituted | Replaces sub-regulation (e) on blank flanges/plugs between safety valve chest and boiler. | listed before the capture |
| 2005-12-15 | G.S.R. 423 OCR of scan | (ff) | Inserted | Inserts clause (ff) applying Appendix JA to boilers of 50 kg/cm2 or more used exclusively for power generation. | listed before the capture |
| 2006-11-08 | G.S.R. 280 | (fff) | Inserted | Inserts clause (fff) applying Appendix JB to captive and waste heat boilers in continuous process plants. | listed before the capture |
| 2007-03-12 | G.S.R. 46 (copy) 2008 web edition | ff | Substituted | Substitutes clause (ff): boilers used only for power generation are inspected under Appendix JA. Uncertain: Text from the unofficial 2008 DIPP web edition; G.S.R. number as published unconfirmed. | listed before the capture |
| 2010-10-07 | G.S.R. 821(E) | Amended | Replaces 'Inspector' with 'Competent Person' wherever it occurs. | listed before the capture |