BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)

Regulation 361 — Wrought Bends

Unofficial DPIIT web edition · not verified3 amendments found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette
Reg. 361

STEAM- PIPES FITTINGS AND CONNECTIONS

Wrought Bends

a)

Pipes of thickness determined in accordance with equation 91 with increase of 12.5% shall not be bent to radii less than those given in the following Table. Where smaller radii are necessary, further allowance shall be made for thinning at the back of the bend except where it can be demonstrated to the satisfaction of the Inspection Authority that the use of tb will not reduce the thickness below t at any point after bending.

Where,

t = min. thickness as per Eq.91
tb = thickness before bending.

TABLE
Minimum bending radii for pipes of thickness determined in accordance with clause (a) of regulation 361.

Outside diameter Radii measured to Centre line of pipe
tb=1.125 t
All thickness
tb=1.1 t
tb=34.92 mm
or above
mm mm mm
20.9 63.5
33.7 76.2
42.4 101.6
48.3 114.3
60.3 152.4
76.1 190.5
88.9 228.6
101.6 266.7
114.3 304.8
127.0 355.6
139.7 381.0
152.4 431.8
168.3 457.2
193.7 635.0
219.1 711.2
244.5 812.8 1143.0
273.0 1016.0 1270.0
298.5 1117.0 1397.0
323.9 1219.2 1524.0
355.6 1498.6 1778.0
406.4 1727.2 2032.0
457.0 2032.0 2086.0
Next >>>
Earlier text: the 2008 DIPP web edition

STEAM- PIPES FITTINGS AND CONNECTIONS

Wrought Bends

a)Pipes of thickness determined in accordance with equation 91 with increase of 12.5% shall not be bent to radii less than those given in the following Table. Where smaller radii are necessary, further allowance shall be made for thinning at the back of the bend except where it can be demonstrated to the satisfaction of the Inspection Authority that the use of tb will not reduce the thickness below t at any point after bending.

Where,

t = min. thickness as per Eq.91

tb = thickness before bending.

                              TABLE
Minimum bending radii for pipes of thickness determined in accordance with clause (a)
                           of regulation 361.

Outside diameter              Radii measured to Centre line of pipe
                                                     tb=1.1 t
                             tb=1.125 t
                                                  tb=34.92 mm
                            All thickness
                                                    or above
         mm                    mm                     mm
20.9                  63.5
33.7                  76.2
42.4                  101.6
48.3                  114.3
60.3                  152.4
76.1                  190.5
88.9                  228.6
101.6                 266.7
114.3                 304.8
127.0                 355.6
139.7                 381.0
152.4                 431.8
168.3                 457.2
193.7                 635.0
219.1                 711.2
244.5                 812.8                 1143.0
273.0                 1016.0                1270.0
298.5                 1117.0                1397.0
323.9                 1219.2                1524.0
355.6                 1498.6                1778.0
406.4                 1727.2                2032.0
457.0                 2032.0                2086.0

                                                                Next >>>

Amendments found

Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.

DateNotificationPartActionWhat changed (summary)Web edition
1993-10-08G.S.R. 516 OCR of scan(c)SubstitutedReplaces the rule on fabricated (gusseted) pipe bends: max 30 degree angle, thickness factor (K-0.5)/(K-1); gusseted bends limited to 21 kg/cm2 and 260 C.listed before the capture
1993-10-08G.S.R. 516 OCR of scan(d)SubstitutedSets minimum radii for forged bends (long 1.5d, short 1.0d) and minimum thickness at any point of the bend.
Uncertain: Operative words substitute only sub-regulation (c), but the quoted text also contains a clause (d).
listed before the capture
2020-09-11G.S.R. 551(E)SubstitutedReplaces regulation 361 (wrought bends).check the text