Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 352 — Copper Pipes
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 352 Copper Pipes
| ||||||||||||||||||||||||||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Copper Pipes
(a)The material shall comply with regulation 35.
b)Copper pipes may be used for maximum design pressure and temperatures as given in the Table below:-
TABLE: Maximum Design Pressure and Temperature for Copper pipes
Material Nominal Maximum Maximum Form
design design
Pressure temperature
Solid drawn Upto and 17.5 207°C Straight or
copper pipes Bend
including kg/cm2
(Steam) 207oC
127mm
12.3
Above 127mm kg/cm2
and including
203mm
Solid drawn
Upto and
copper pipes 21 kg/cm2 149°C
including 203mm
(feed)
c)Copper pipes shall not be used for superheated steam.
d)The maximum working pressure on such pipes shall be deter-mined by the following formula:-
200 x S x t
WP = Eqn.(93)
D - t
where,
WP = working pressure in kg/mm²
t = minimum thickness of tubes, that is nominal thickness less the permissible negative tolerance in mm.
D = outside diameter of pipe in mm.
S = maximum permissible design stress at the appropriate maximum design temperature in kg/mm²
(See the Table below)
Maximum Design Stress Value of S for Copper pipes (in kg. per sq. mm)
Maximum design stress for temperature not exceeding
66°C 121°C 149°C 177°C 207°C 4.9 4.31 3.5 2.66 1.75
Note: Where the conditions of services are such that corrosion, erosion or mechanical damage to the surface of tubes may occur, an appropriate thickness allowance shall be added to the minimum thickness of the tube.
Possible IBR 2026 successors (heading match, unverified): Reg. 249