Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 346 — MECHANICAL TESTS
Unofficial DPIIT web edition · not verified0 amendments found
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette
| Reg. 346 MECHANICAL TESTS Number of sets of tests
|
Earlier text: the 2008 DIPP web edition
MECHANICAL TESTS
Number of sets of tests
The number of pipes on which mechanical tests shall be performed shall be as follows:-
Seamless pipes:
Up to and including 114 mm. As per requirements of Chapter II. (4-1/2 in.) o. d.
Over 114 mm. o. d. 5 per cent of the lengths of pipe as
made, or 2 per cent of the pipes from
each cast where the cast (i.e. melt)
can be identified.
Welded pipes 2 per cent of the lengths of pipes as
made.
In the case of pipes for designed temperatures over 454°C (850°F) every pipe over 114 mm. (4-1/2 in.) outside diameter shall be tested.
Possible IBR 2026 successors (heading match, unverified): Reg. 53, Reg. 153, Reg. 252, Reg. 509