Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 332 — Type
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 330, 331, 333. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 330, Reg. 331, Reg. 332, Reg. 333 | ||||||||
|
Reg. 331 FUSIBLE PLUGS General
Reg. 332 Type
Reg. 333 Material
|
Earlier text: the 2008 DIPP web edition
Type
Fusible plugs shall consist of an outer body with a central conical passage the smallest part to be not greater than 1/2 inch for plugs suitable for pressure up to 100 lbs. per sq. in. and not greater than 3/8 inch for plugs for pressures exceeding 100 lbs. per sq. in. The passage shall be closed by a plug secured by an annual lining of fusible alloy so that the plug may drop clear if the lining melts.
The portion of the body carrying the fusible metal should preferably be detachable from the base to allow of easy replacement without removing the whole fitting from the boiler.