Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 309 — Determination of Working Pressure
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 308, 307B. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 307 B, Reg. 308, Reg. 309 | |||||||||||||||||
Reg. 308 Dimensions
Reg. 309 Determination of Working Pressure
|
| Next >>> |
Earlier text: the 2008 DIPP web edition
Determination of Working Pressure
1.The maximum working pressure to be allowed for steel springs of round, square or rectangular section shall be determined from the following formulae:-
For Springs in Extension.
(a)Round section: -
W.P.= 10,000 π d³ Eqn. (80)
DACK
(b)Square section: -
33,333 d³
W.P.= Eqn. (81)
DACK
(c)Rectangular section: -
160,000 B² H²
W.P.= Eqn. (82)
DACK (3B+1.8H)
where all dimensions in inches
For Springs in Compression.- The working pressure calculated by the above equation may be increased by 25 per cent.