Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 308 — Dimensions
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 309, 307B. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 307 B, Reg. 308, Reg. 309 | |||||||||||||||||
Reg. 308 Dimensions
Reg. 309 Determination of Working Pressure
|
| Next >>> |
Earlier text: the 2008 DIPP web edition
Dimensions
For ordinary lift valves, the compression or extension of safety valve springs required to load the valves to the set pressure shall not be less than one quarter of the diameter of the valve due consideration being given in the case of spring loaded lever safety valves to the ratio of leverage. The proportion of unloaded length to external diameter of the spring shall not exceed 4:1.
These requirements do not apply to full lift and high lift safety valves.