Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 277 — Dished End with Opening
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 276. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
|
| ||||||||||||||||||||||||||||||||
Reg. 277
| ||||||||||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
Dished End with Opening
a)Heads with openings:-
i)Holes cut in the heads (manholes or tube holes) should be round or elliptical.
ii)Small size openings complying with conditions of sub-regulation (c) do not require any additional thickness of head or reinforcement of opening.
iii)Large size openings require an increase in thickness of the head, according to sub-regulation (b) or a reinforcement of the opening according to sub-regulation (d).
b)Shape factor K for heads with large unreinforced openings:- The shape factor K to
be used in calculating the thickness of heads varies depending on the height of the
head H and on the dimensions of the largest opening. The value of K is indicated
in Fig. 23D, by means of curves, each of which corresponds to a value of the
ratio.-
d
---------
√ D T
where,
d = diameter of the largest opening in the head (in the case of an elliptical opening, the larger diameter of the ellipse);
D = outside diameter of the head; and
T = minimum thickness after dishing.
In addition, the following conditions shall be satisfied:
T
< 0.1
D
d
< 0.5
D
The same condition and the same curves apply for openings simply cut in the plate of the head as well as to those which are flanged inwards. In the latter case, the radius r’ of the flanging (see Fig. 23C) should not be smaller than 25 mm (1 inch). The thickness of the flanged portion may be smaller than the calculated thickness T.
Unreinforced openings and flanged-in openings in dished heads shall be arranged so that the distance from the edge of the head is not less than as shown in Fig. 23E.
In all cases the width of the band separating two adjacent openings should, in projection, be at least equal to the diameter of the smallest opening as shown in Fig. 23E.
c)Small openings which do not require any reinforcement:-
Figure 23D indicates that for a given ratio of H/d, the shape factor K of a plain head corresponds to a certain values of the ratio,
d (DT)¹ᐟ²
Piercing of holes with a diameter smaller than or equal to that which corresponds to this value can thus be made without any reinforcement in a head, the thickness of which is equal to the minimum required for a plain head.
The position of those openings shall however comply with the conditions stated in sub-regulation (b).
d)
Reinforcement of large openings:-Large holes may be cut without increasing the thickness of the head, provided they are sufficiently reinforced.
The reinforcement may consist either of a welded nozzle or one or two reinforcing welded plates, or of a combination of these two procedures.
To determine the strength of the construction, one shall proceed as follows (see Fig. 23F). Let the imaginary diameter d’ of the opening be given by the formula
A
d' = d -
T
where,
d = actual diameter of the opening in the head (outside diameter of the nozzle);
T = minimum thickness of the head; and
A = effective cross-section of reinforcement.
This effective area A corresponds, within the Limits given below, with the actual cross-section of the reinforcing plates and with the cross-section of the nozzle decreased by the cross-section necessary to support the pressure, for those parts of the nozzle situated outside the internal surface of the head.
The shape factor K can then be read corresponding to the ratio
d (DT)¹ᐟ²
The maximum limits for the are of reinforcement that should be taken into account are
(a)L1 = (2 RT)¹ᐟ². for the width of a reinforcing plate;
(b)L2 = (d Tt)¹ᐟ² for the length of a nozzle.
where,
R = internal radius of the spherical part of the head (or for elliptical heads the internal radius of curvature of the meridian at the centre of the opening)
Tt = actual thickness of the nozzle,
L1 and L2 = dimensions given in Fig. 23F.
The position of the outer edges of the reinforcement shall comply with the provisions of sub-regulation (b) and Fig. 23E.
In cases where the allowable stress of a part of the reinforcement is lower than that of the head, the corresponding area A should be multiplied by the ratio:
allowable stress of the reinforcement material
--------------------------------------------------------------------------------------
allowable stress of the head materialAmendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 1995-01-27 | G.S.R. 93 OCR of scan | Substituted | Replaces regulation 277 on dished ends with openings: shape factor K, small openings, and reinforcement of large openings. | listed before the capture |