Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 243A — Tolerance
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 241, 242, 243. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
|
Additional tests before rejection | |||||||||||||
Reg.242 Discard
Reg.243 Forging
Reg.243A Tolerance
| |||||||||||||
Earlier text: the 2008 DIPP web edition
Tolerance
a)The deviation from circularity in any section shall, in the case of normalised drums, not exceed 2% and in case of stress relieved drum 1%. The deviation from a straight line shall not exceed 0.3% of the cylindrical length.
b)In order to determine the deviation from circularity of the drums the maximum and minimum internal diameter at one cross section shall be measured. From these measured values the percentage deviation from circularity shall be calculated according to the following formula:-
2(dmax – dmin)
C = x 100
(dmax + dmin)
where,
C = percentage deviation from circularity of the drums.
d = internal diameter at one cross section.
In order to determine the deviation from a straight line, a stretched line should be placed longitudinally against the sides and its largest distance from the shell line concerned shall be measured. From this distance, and from the cylindrical shell, the deviation from the straight line shall be calculated.