BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)

Regulation 156 — Design of stand pipes

Unofficial DPIIT web edition · not verified2 amendments found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette
Reg. 156
STAND PIPES, PADS ETC.

Design of stand pipes.-The design of the branches and standpipe shall be regulated in the following manner:

(a)  in order to withstand the maximum working pressure or design pressure, the     minimum thickness of branch and standpipe shall be determined in accordance with the provisions specified in sub-regulation (a) of regulation 338;

(b)  compensation requirements for openings in the main pressure parts shall be determined in accordance with the provisions of regulation 279;

(c)  the additional thickness shall be considered to withstand superimposed loading due to connecting pipe-work or fittings.

The minimum thickness of the branch or stand-pipe shall be the greatest of the values required above and shall not be less than 0.015 do + 3.2 mm where do is the outside diameter of the branch (in mm.):

Providedthat the provisions of the regulations shall not apply to such tube stub which have been designated as tubes.

Earlier text: the 2008 DIPP web edition

STAND PIPES, PADS ETC.

GENERAL

Design of stand pipes

The design of the branches and standpipe shall be regulated in the following manner:

a)in order to withstand the maximum working pressure or design pressure, the minimum thickness of branch and standpipe shall be determined in accordance with the provisions specified in sub-regulation (a) of regulation 338;

b)compensation requirements for openings in the main pressure parts shall be determined in accordance with the provisions of regulation 279;

c)the additional thickness shall be considered to withstand superimposed loading due to connecting pipe-work or fittings.

The minimum thickness of the branch or stand-pipe shall be the greatest of the values required above and shall not be less than 0.015 do + 3.2 mm where do is the outside diameter of the branch (in mm.)

Provided that the provisions of the regulations shall not apply to such tube stub which have been designated as tubes.

Amendments found

Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.

DateNotificationPartActionWhat changed (summary)Web edition
1999-04-16G.S.R. 131SubstitutedReplaces regulation 156 (Design of stand pipes) with new rules on branch and standpipe thickness, compensation for openings and superimposed loads.listed before the capture
1999-04-16G.S.R. 131ChangedErratum (March 2001) corrects the minimum thickness expression from 0.15 do to 0.015 do plus 3.2 mm.
Uncertain: Erratum is printed with this notification; the official chain attaches an erratum (G.S.R. 201, 7 Apr 2001) to G.S.R. 139 instead.
listed before the capture