Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 129 — Loco Type Fireboxes
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 129 FURNACES Loco Type Fireboxes
|
Earlier text: the 2008 DIPP web edition
FURNACES
GENERAL
Loco Type Fireboxes
a)The foundation seam shall be of riveted construction but all other seams may be welded subject to the depth of the flange being such that the welded seams fall between the 1st and 2nd rows of screwed stays or between the flange and the adjacent row screwed stays.
b)The firehole mouthpiece may be similarly welded when the firebox and shell are flanged for the purpose.
c)The welding shall comply with Regulation 125.
d)The welding of copper fireboxes shall comply with the following regulation.