Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 119 — Parts of flat tube plates within the tube nests
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 118, 120. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 118, Reg. 119, Reg. 120 END PLATES
Tube Plates Parts of flat tube plates within the tube nests
Reg. 120 END PLATES Flanging of End Plates All flanges shall be a good fit to the shell and flues. Flogging and/or hammering in the fitting of these parts is prohibited. The caulking edges of all flanged plates shall be machined or machine gas cut. |
Earlier text: the 2008 DIPP web edition
END PLATES
GENERAL
Parts of flat tube plates within the tube nests
a)where the total area of all tube nests in directly fired multi-tubular boilers exceeds 7 sq. ft., stay tubes shall be fitted.
Where the total number of tubes in horizontal multitubular waste heat boilers and direct fired loco type boilers is arranged in one nest, the area of which exceed 21 sq. ft., stay tubes shall be fitted.
In all cases where the total number of tubes is arranged in more than one nest, stay tubes shall be fitted.
b)The parts of tube plates which lie outside the nests of tubes shall be stayed or supported wherever the size of the area of plate subject to steam pressure necessitates staying or support, either by marginal stay tubes or other means.