BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Original IBRsource drawing · explanatory drawing + 3-D teaching model

Joining plates of unequal thickness: the 1 : 8 taper (rule of Fig. 12/1)

Dimensioned example geometry (not a design)Educational — not an approved or fabrication-ready designTechnical review pending — not independently verified
Section of a thin plate butt-welded to a thicker plate whose top surface tapers at 1 in 8 over length L, with a 3-D view.

Explains the taper rule printed in Gazette Fig. 12/1 (L = 8 (T₂ − T₁), not less than 38.1 mm) with a worked example, a section, a 3-D FreeCAD model and a DXF.

Download

SVG — vector, for screens · PNG — image · PDF — print · DXF — 2-D CAD · FCStd — FreeCAD source · STEP — 3-D solid

Related provisions

Regulation 86 · Regulation 402

Basis
Hypothetical T1=12, T2=20 mm; L = max(8(T2-T1), 38.1) = 64 mm measured from the weld centre line to full T2 (as in Fig. 12/1); plates 200 mm wide.
Units
mm
Limitations
Weld shown schematically (two square plate edges with weld metal between); no groove preparation, root gap or NDT requirements implied.
Tool
FreeCAD 1.1.4 (headless, scripted) + Python/ezdxf
Licence
CC BY 4.0 for this original drawing/model. Does not license the regulation text or Gazette figures.
Revision
v1.0 · 2026-11-20 · technical review: pending
Automated checks
L_rule_mm: 64
L_ge_38_1: true
L_over_rise: 8
L_measured_from: weld centre line (Fig. 12/1)
STEP volume deviation: 0%
DXF file structure check: 0 audit errors
File checks only; they do not verify technical accuracy, dimensions or compliance.
File checksums
SHA-256 per file
  • SVG: f2ae723eb78578cc55b899c8709058dcacbff3a053a0acedfd571f170077570f
  • PNG: 1bfb76d3e459e60efb0e6379c720495bdbbb72164de0ce653007234b33ef0c72
  • PDF: b738279afc3d847dba3eadf1dcac35f1479429a366bee94b636433dfaaaa7586
  • DXF: 2042c8ada023c7239f72e3c88b5e931e3abcc78b342366f639d6ea32dbdc1112
  • FCSTD: 81f052a79bb97ab396190380b3ccafa62c6a543fea79366620666eeb75f0a35f
  • STEP: b336f10dc84b8be09d867b2323439af5238f628df0be01ab8e9916e1d7a4991e

The small IBRsource.com mark sits on its own layer (DXF), object (FreeCAD) or group (SVG) and can be deleted. The CC BY 4.0 attribution requirement still applies if you remove it.

Educational drawing, not an approved or fabrication-ready design; verify against the Gazette (report a problem).