Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 579D — Plain tubes
Unofficial DPIIT web edition · not verified0 amendments found
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 579C. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette
| Reg. 579 c, Reg. 579 d | ||||||||||||||||||||||||||||||||||||||||
Reg. 579 d Plain tubes
|
Earlier text: the 2008 DIPP web edition
Plain tubes
Internal Pressure: -
The thickness of tubes under internal pressure shall be calculated as under:
WP .D
t = + C Equation XII/15
WP + 2f
Where,
WP = Internal working pressure, kg/cm² (g), and other symbols as per clarifications indicated at (a) above.
In no case the thickness of straight tubes under internal pressure shall not be less than listed below:
Tube outside diameter Minimum thickness
(mm) (mm)
Not exceeding 39 1.75
Exceeding 39 but not exceeding 51 2.16
Exceeding 51 but not exceeding 70 2.4
Exceeding 70 but not exceeding 77 2.6
Exceeding 77 but not exceeding 96 3.05
Exceeding 96 but not exceeding 102 3.28
Exceeding 102 but not exceeding 127 3.5