Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 555D — Seatings for Mountings
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 555 d | |||||||||||||||||
Attachment of Standpipes
| |||||||||||||||||
Earlier text: the 2008 DIPP web edition
Seatings for Mountings
Attachment of Standpipes
The following constructions as to stand-pipes attached to shells and end plates shall be permissible:
i)When the internal diameter of the standpipe does not exceed 1 inch, the standpipe may be screwed into the plate with a nut on the waterside.
ii)Where the internal diameter of the standpipe exceeds one inch but does not exceed 2 inches, it may be screwed in and seal-welded.
iii)Where the diameter of the standpipe exceeds 2 inches, it may be welded to the end plate.
The foregoing provisions as to the standpipe attachment shall be regulated by the following conditions:-
i)When standpipes are screwed, the screwing shall be of standard pipe thread.
ii)Standpipes shall be attached by one of the methods shown in Figures XII/84, XII/85(A,B,C),XII/85D,XII/85E,XII/85F,XII/86, XII/87, XII/88, XII/89 and XII/93 or by any other method approved by the Inspecting Authority.
iii)Where the standpipes are fabricated by fusion-welding they shall be stress relieved by heat-treatment before attachment to the boiler unless the whole boiler is subject to heat-treatment on completion.
iv)Where the bore of the standpipe does not exceed 5 inches or the diameter of the opening in the shell does not exceed 5 inches plus twice the thickness of the plate to which it is attached, the standpipe may be welded to the plate without subsequent heat-treatment of the weld so made. If these limits are exceeded the whole plate to which the standpipe is attached shall be stress relieved by heattreatment on completion of welding.