Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 544 — Circularity
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 542, 543. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 542, Reg. 543, Reg. 544
Reg. 543
Reg. 544
| ||||||||||||||||
Earlier text: the 2008 DIPP web edition
Circularity
The difference between the maximum and minimum internal diameters of the shell measured at any one cross section shall not exceed 1 per cent of the nominal internal diameter.
The profile as measured on the outside of the boiler by means of a gauge of the designed form of the exterior of the boiler, having a length equal to one quarter of the internal diameter, shall not depart from the designed form by more than the percentage given in Table XII/1.
TABLE XII/1
Maximum percentage departure from designed form of welded boilers
Nominal internal diameter of boiler D Maximum departure from designed form
Inches Per cent
Up to and including 36 0.375
Over 36, up to and including 45 0.350
Over 45 0.300
There shall be no flats at the welded seams and any local departure from circularity shall be gradual.