BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)

Regulation 53C — Workmanship and tolerance

Unofficial DPIIT web edition · not verified0 amendments found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette
Reg. 53 c
MATERIALS OF CONSTRUCTION

SEAMLESS FERRITIC PIPES FOR HIGH TEMPERATURE SERVICE

Workmanship and tolerance

The pipes shall be well finished, cleaned free from harmful defects.  They shall be reasonably straight, smooth, cylindrical and subject to the following tolerances.  Pipes manufacturer shall explore a sufficient number of visual inspections to provide reasonable assurance that they have been properly evaluated. 

(i) Permissible variation in outside diameter. 

For all grades except X20CrMoV121

Hot finished and Cold finished seamless pipes

Outside diameter (mm)     

Permissible variations (mm)

Over

Under

10.3 to 48.3 incl.

0.40

0.40

Over 48.3 to 114.3 incl.

0.79

0.79

Over 114.3 to 219.1 incl.

1.58

0.79

Over 219.1 to 300 incl.

2.38

0.79

Over 300.

1%

1%


Earlier text: the 2008 DIPP web edition

MATERIALS OF CONSTRUCTION

SEAMLESS CHROMIUM-MOLYBDENUM STEEL BOILER AND SUPER HEATER TUBES FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 538 DEGREE C (1,000 DEGREE F).

Workmanship and tolerance

The tubes shall be well finished, clean and free from harmful defects. They shall be reasonably straight, smooth, cylindrical and subject to the following tolerances before bending:-

Diameter.- The external diameter of the tubes measured at any point shall be within the

(i)following tolerances of the diameter specified:-

Type of Tube     Outside Diameter of Tube          Tolerance
Hot finished    Upto and including 2½ inches        + 1/64”
                                                    - 1/32”
                      Over 2½ inches                 + 1%
                                                     - 1%
 Cold drawn              All sizes                   + 0%
                                                     - 1%

(ii)Thickness.- The thickness of the tubes shall be within the following tolerances:-

Type of Tube       Outside Diameter of Tube          Tolerance
 Hot finished     Upto and including 2½ inches        + 17½%
                                                      - 7½%
                     -------------------------------  ------------------
                                                      + 15%
                        Over 2½ inches                 - 5%

 Cold drawn                All sizes                  + 10%
                                                       - 5%

Where the ends of the tubes are swelled or reduced, the thickness at the ends may be decreased below or increased above the nominal thickness of the tubes by an amount in proportion to the percentage of such swelling or reduction and, in addition to this allowance, the tolerances relating to thickness shall also apply. Swelling or reduction shall be carried out before the heat-treatment specified in Regulation 53(b).

(iii)Length.- The length of the tubes shall be not less than the nominal length, but may exceed it by the amount given below:

Upto and including 30 ft               1/8 inch
Over 30 ft                             ¼ inch