Regulation 53C — Workmanship and tolerance
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 53 c MATERIALS OF CONSTRUCTION SEAMLESS FERRITIC PIPES FOR HIGH TEMPERATURE SERVICE |
| The pipes shall be well finished, cleaned free from harmful defects. They shall be reasonably straight, smooth, cylindrical and subject to the following tolerances. Pipes manufacturer shall explore a sufficient number of visual inspections to provide reasonable assurance that they have been properly evaluated. (i) Permissible variation in outside diameter. For all grades except X20CrMoV121
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Earlier text: the 2008 DIPP web edition
MATERIALS OF CONSTRUCTION
SEAMLESS CHROMIUM-MOLYBDENUM STEEL BOILER AND SUPER HEATER TUBES FOR DESIGN METAL TEMPERATURES NOT EXCEEDING 538 DEGREE C (1,000 DEGREE F).
Workmanship and tolerance
The tubes shall be well finished, clean and free from harmful defects. They shall be reasonably straight, smooth, cylindrical and subject to the following tolerances before bending:-
Diameter.- The external diameter of the tubes measured at any point shall be within the
(i)following tolerances of the diameter specified:-
Type of Tube Outside Diameter of Tube Tolerance
Hot finished Upto and including 2½ inches + 1/64”
- 1/32”
Over 2½ inches + 1%
- 1%
Cold drawn All sizes + 0%
- 1%
(ii)Thickness.- The thickness of the tubes shall be within the following tolerances:-
Type of Tube Outside Diameter of Tube Tolerance
Hot finished Upto and including 2½ inches + 17½%
- 7½%
------------------------------- ------------------
+ 15%
Over 2½ inches - 5%
Cold drawn All sizes + 10%
- 5%
Where the ends of the tubes are swelled or reduced, the thickness at the ends may be decreased below or increased above the nominal thickness of the tubes by an amount in proportion to the percentage of such swelling or reduction and, in addition to this allowance, the tolerances relating to thickness shall also apply. Swelling or reduction shall be carried out before the heat-treatment specified in Regulation 53(b).
(iii)Length.- The length of the tubes shall be not less than the nominal length, but may exceed it by the amount given below:
Upto and including 30 ft 1/8 inch Over 30 ft ¼ inch