Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 520 — FEED PIPES
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 521, 522. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 520, Reg. 521, Reg. 522 FEED PIPES | |||||||||
| |||||||||
|
FEED PIPES | |||||||||
| |||||||||
| Reg. 522 FEED PIPES | |||||||||
|
Earlier text: the 2008 DIPP web edition
STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS
FEED PIPES
General
Feed pipers may be made of steel, cast iron or copper cut cast iron pipes will not be accepted for a working pressure over 200 lbs. per sq. in. or 425°F. Copper feed pipes shall be solid drawn and not exceeding 8” external diameter and may be used for a working pressure not exceeding 350 lbs. or 300°F.
Design pressure for feed piping:-
The design pressure shall be the maximum pressure generated in overcoming friction and other losses in the feed piping under ordinary working conditions, or the maximum pressure which can be generated by the boiler feed pumps unless special provision is made to prevent that pressure being communicated to the pipe line.
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 2007-03-12 | G.S.R. 46 (copy) 2008 web edition | Amended | Inserts a note on feed-water discharge piping without an economiser inlet isolating valve for boilers at 100 kg/cm² and above. Uncertain: Text from the unofficial 2008 DIPP web edition; G.S.R. number as published unconfirmed. | listed before the capture | |
| 2015-04-15 | G.S.R. 286(E) | Amended | Adds a three-way valve for bypassing the HP heater in the Note. | listed before the capture |