BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)

Regulation 520 — FEED PIPES

Unofficial DPIIT web edition · not verified2 amendments found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 521, 522. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette

Reg. 520, Reg. 521, Reg. 522
STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

FEED PIPES

General
Feed pipers may be made of steel, cast iron or copper cut cast iron pipes will not be accepted for a working pressure over 200 lbs. per sq. in. or 425°F. Copper feed pipes shall be solid drawn and not exceeding 8” external diameter and may be used for a working pressure not exceeding 350 lbs. or 300°F.

Design pressure for feed piping:-

The design pressure shall be the maximum pressure generated in overcoming friction and other losses in the feed piping under ordinary working conditions, or the maximum pressure which can be generated by the boiler feed pumps unless special provision is made to prevent that pressure being communicated to the pipe line.


Reg. 521

STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

FEED PIPES

Steel feed pipes
Steel feed pipes shall be in accordance with Chapter VIII.

Reg. 522
STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMIZER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

FEED PIPES

Cast Iron feed pipes
a) The standard conditions for material of construction and tests for cast iron pipes shall comply with Regulation 505 to 509.
b) The maximum working pressure shall be determined by the following formula:-

W.P. = 130(t-6) Eqn.(122)
d


Where,

t=thickness in thirty second of an inch.
d=the external diameter of the pipe in inches.
Earlier text: the 2008 DIPP web edition

STANDARD CONDITIONS FOR THE DESIGN AND CONSTRUCTION OF ECONOMISER, FEED PIPES, FEED HEATERS AND OTHER SIMILAR VESSELS

FEED PIPES

General

Feed pipers may be made of steel, cast iron or copper cut cast iron pipes will not be accepted for a working pressure over 200 lbs. per sq. in. or 425°F. Copper feed pipes shall be solid drawn and not exceeding 8” external diameter and may be used for a working pressure not exceeding 350 lbs. or 300°F.

Design pressure for feed piping:-

The design pressure shall be the maximum pressure generated in overcoming friction and other losses in the feed piping under ordinary working conditions, or the maximum pressure which can be generated by the boiler feed pumps unless special provision is made to prevent that pressure being communicated to the pipe line.

Amendments found

Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.

DateNotificationPartActionWhat changed (summary)Web edition
2007-03-12G.S.R. 46 (copy) 2008 web editionAmendedInserts a note on feed-water discharge piping without an economiser inlet isolating valve for boilers at 100 kg/cm² and above.
Uncertain: Text from the unofficial 2008 DIPP web edition; G.S.R. number as published unconfirmed.
listed before the capture
2015-04-15G.S.R. 286(E)AmendedAdds a three-way valve for bypassing the HP heater in the Note.listed before the capture