Regulation 437 — Mountings, Fittings and Connections (For all types of Electrode Boilers)
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 435, 436. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 435, Reg. 436, Reg. 437
Reg. 436
Reg. 437
|
Earlier text: the 2008 DIPP web edition
SEAMLESS SHELL BOILERS
Mountings, Fittings and Connections (For all types of Electrode Boilers)
Mountings, fittings and connections shall comply with Regulation 281.
In the case of electrode boilers one means of indicating water level of the tubular water level gauge-glass type and one means of feeding the boiler shall suffice and the Safety Valves shall be of spring loaded type.
If an Electrode boiler is fitted with a magnetic valve, the said valve will be accepted in lieu of the second safety valve, provided the source of power supply to both the valve and the boiler is the same and both are operated by one single switch.