Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 425 — Determination for Working Pressure
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 424, 426. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 424, Reg. 425, Reg. 426
Reg. 425
Reg. 426
|
Earlier text: the 2008 DIPP web edition
TESTS FOR CLASS II FUSION WELDED SEAMS
Determination for Working Pressure
The working pressure of cylindrical shells with fursion welded seams shall be calculated from the following formula:-
(t-2) x S x C
W.P. = Equation (99)
D
Where,
t = thickness of shell plate in thirty-seconds of an inch.
D = internal diameter of shell in inches.
S = Ultimate tensile stress in tons per square inch.
C = 32 for Class I boilers.
C = 27 for Class II boilers.
In no case the thickness of cylindrical shells with fusion welded seams be less than those given in table below:-
Minimum thickness for Fusion Welded Shells
Class Internal diameter inches Minimum thickness inches
Up to and including 24 ¼
Over 24 up to and including
II 5/16
36
Over 36 3/8
In no case shall the factor of safety of the cylindrical shell and ends be less than 4.