Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 390L — Pipe Connections and Fittings
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 390J, 390K. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 390 j
Reg. 390 k
Reg. 390 l
|
Earlier text: the 2008 DIPP web edition
Pipe Connections and Fittings
The steam and water pipes, including connections to the water column, shall be examined for leaks, and if any are found it should be determined whether they are the result of excessive strains due to expansion and contraction, or other causes. The general arrangement of the piping in regard to the provisions for expansion and drainage, as well as adequate support at the proper points, shall be carefully noted. The location of the various stop valves shall be observed to see that water will not be pocketed when the valves are closed and thereby establish cause for water-hammer action.
The arrangement of connections between individual boilers and the main steam pipes shall be especially noted to see that any change of position of the boiler due to setting or other causes, will not produce an undue strain on the piping.
It shall be ascertained whether all pipe connections to the boiler possess the proper strength in their fastenings, whether tapped into the boiler, a fitting, or flange riveted to the boiler.
The Inspector shall determine whether there is proper provision for the expansion and contraction of such piping, and that there is no undue vibration tending to crystallize the parts subjected to it. This includes all steam and water pipe; and special attention should be given to the blow off pipes with their connections and fittings, because the expansion and contraction due to rapid changes in temperature and water-hammer action create a great strain upon the entire blow off system, which is more pronounced when a number of blow off pipes are joined in one common discharge. The freedom of the blow off connection on each boiler shall be tested whenever possible by opening the valve for a few seconds, at which time it can be determined whether there is excessive vibration. Blow off pipes should be free from external dampness to prevent corrosion.