Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 316 — Steam Stop Valve
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 313, 314, 315. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 313, Reg. 314, Reg. 315, Reg. 316 | ||||||||||||
Reg. 314 Finishing of Ends
Reg. 315 STOP VALVES Lever Valves
Reg. 316 Steam Stop Valve
|
Earlier text: the 2008 DIPP web edition
Steam Stop Valve
a)The stop valve connecting the boiler or supper heater to the steam-delivery pipe shall be located as near the out-let from the final super-heater header as is convenient and practicable or in case of boilers without super-heaters as close as practicable to the drum, where two or more boilers are connected with a steam receiver or any other vessel, a steam stop valve shall be fitted between the boiler and such receiver or Vessel.
b)Steam stop valves shall be attached direct to the boiler shell or to suitable pads or stand blocks and the neck or the valve chest shall be reasonably short and of strong construction. The steam stop valve may also be attached to a stand pipe, a connecting pipe or the superheater header. The attachment may be made by bolted flanges or butt-welded joints. Such butt-welded joints shall be suitably stress relieved, where necessary:
Provided that in the case of a larger boiler in which it is proposed for the purpose of drainage or owing to obstruction, to connect the steam-pipes to the steam stop valve at a higher level than would be obtained under this Regulation, a vertical stand pipe not exceeding 5 diameters in height will be permitted between the step valve and the boiler. Such stand pipes shall be of strong construction and of wrought iron, mild steel, or cast steel. The flanges of wrought iron or mild steel, or cast steel. The flanges of wrought iron or mild steel pipes shall be riveted or welded to the pipes, and there shall be no branch on the stand pipe for any other connection:
Provided also that in the case of large boiler in which it is desired to fit a tee piece for the purpose of providing a branch connection between the stop valve and the boiler, such a tee piece may be so fitted. The tee piece shall be of strong construction, of wrought iron, mild steel, or cast steel and shall not exceed 2½ diameters in height. A stop valve shall be fitted direct to each tee piece branch.
c)Wedge type valves the sealing surfaces of which are solidly connected with the
wedge, shall not be permitted for steam service.
d)when two or more boilers are connected to a common steam main and there are no combined stop and isolating valves fitted to them, an automatic isolating valve shall be compulsory. In the case of boilers fitted with welded pipes, fitting of an independent automatic isolating valve shall be compulsory.