Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 282B — Limits of cast Iron
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 282C. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 282 b, Reg. 282 c
Reg. 282 c Limits of copper alloy
|
Earlier text: the 2008 DIPP web edition
Limits of cast Iron
Cast Iron shall not be used for: -
a)Temperatures above 220°C;
b)Pressure exceeding 13 bar guage;
c)Valves exceeding 200 mm nominal bore which are connected directly to the boiler;
d)Wedge or double disc gate valves which are connected directly to the boiler;
e)Boiler blow down fittings.
Explanation: The expression ‘connected directly to the boiler’ covers any valve which cannot itself be isolated from the boiler.
Note:-
Spherodial iron may be used for temperature not exceeding 282 °C and pressure not exceeding 17.58 kg/cm² provided it complies with the following requirements in respect of the physical properties.
(a)0.2% proof stress 250 kg/mm²
(b)minimum elongation percent-12.