Regulation 282B — Limits of cast Iron

Unofficial DPIIT web edition · not verified0 amendments found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 282C. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette

Reg. 282 b, Reg. 282 c

(b) Limits of cast Iron

Cast Iron shall not be used for: -

a) Temperatures above 220°C;
b) Pressure exceeding 13 bar guage;
c) Valves exceeding 200 mm nominal bore which are connected directly to the boiler;
d) Wedge or double disc gate valves which are connected directly to the boiler;
e) Boiler blow down fittings.

Explanation: The expression ‘connected directly to the boiler’ covers any valve which cannot itself be isolated from the boiler.

Note:-
Spherodial iron may be used for temperature not exceeding 282 °C and pressure not exceeding 17.58 kg/cm2 provided it complies with the following requirements in respect of the physical properties.

(a) 0.2% proof stress 250 kg/mm2
(b) minimum elongation percent-12.


Reg. 282 c

Limits of copper alloy

Copper alloy shall not be used for temperatures above 225°C where the valves are connected directly to the boiler. In the case of valves not connected directly to the boiler this temperature limitation may be increased to 260°C.
Earlier text: the 2008 DIPP web edition

Limits of cast Iron

Cast Iron shall not be used for: -

a)Temperatures above 220°C;

b)Pressure exceeding 13 bar guage;

c)Valves exceeding 200 mm nominal bore which are connected directly to the boiler;

d)Wedge or double disc gate valves which are connected directly to the boiler;

e)Boiler blow down fittings.

Explanation: The expression ‘connected directly to the boiler’ covers any valve which cannot itself be isolated from the boiler.

Note:-

Spherodial iron may be used for temperature not exceeding 282 °C and pressure not exceeding 17.58 kg/cm² provided it complies with the following requirements in respect of the physical properties.

(a)0.2% proof stress 250 kg/mm²

(b)minimum elongation percent-12.