BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)

Regulation 274 — Intermediate Boiler Drum Supports

Unofficial DPIIT web edition · not verified0 amendments found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulation 275. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette


Reg. 274, Reg. 275

Intermediate Boiler Drum Supports

Where a boiler drum is supported at intermediate points in its length at a distance greater than one internal diameter from the end of the parallel portion of the drum shell, the shell shall be thickened locally to the support or so designed that when the local stress set up by the supports in the drum shell are added, algebraically to those caused by the internal steam pressure and supported loads, the maximum resultant stress does not exceed the permissible working stress at the working metal temperature.


Reg. 275
END PLATES

Shape of Dished End Plate

When the end plate is dished to semi ellipsodial, partial-spherical or hemispherical form, it shall comply with the following (see Figure 23A, 23B, 23C)

a)  hemispherical heads without limitation;
b) elliptical heads sufficiently dished so that H ³ 0.2 D;
c) partial spherical heads satisfying all the following requirements:

r ³ 0.1 D
r ³ 3 T
R £  D
H  ³ 0.18D

A value of R< 1.2 D is permitted for ends in which the ratio H/D falls between 0.18 - 0.2.

In accordance with Figs. 23A, 23B, 23C, 23D, 23E, 23F.

D = outside diameter of the head;
H = height of the head measured on its outside surface from the junction of the dished part with the cylindrical shell;
R = inside radius of the spherical part of partial spherical heads;
r = inside knuckle radius of partial spherical heads.

Earlier text: the 2008 DIPP web edition

Intermediate Boiler Drum Supports

Where a boiler drum is supported at intermediate points in its length at a distance greater than one internal diameter from the end of the parallel portion of the drum shell, the shell shall be thickened locally to the support or so designed that when the local stress set up by the supports in the drum shell are added, algebraically to those caused by the internal steam pressure and supported loads, the maximum resultant stress does not exceed the permissible working stress at the working metal temperature.