Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 240E — Bend Tests
Unofficial 2008 web edition · not verified0 amendments found
Text in the 2008 DIPP web edition
saved copy p.249, as amended to about 2005 (later amendments below are not merged; units as printed).
Unofficial DIPP web edition (2008) · machine-extracted · not checked against the Gazette
Bend Tests
The test pieces shall, when cold, be capable of being bent without fracture, through an angle of 180°, the internal radius of the bend being not greater than that specified in table below:-
Internal radius of bend in inches Upto 32 3/8
Above 32 and upto 36 ½
Above 36 and upto 38 ¾
Bend tests may be made by pressure or, by blows.