| Reg. 216, Reg. 217, Reg. 218, Reg. 219 BOILER AND SUPERHEATER TUBES SUBJECT TO INTERNAL PRESSURE The maximum working pressure for the tube shall be determined by equation No.87 (see Regulation 338). The maximum thickness of the tubes shall comply with the table given in Regulation 338 (b).
Where t = the thickness of the tubes in 100ths of an inch, D = the external diameter of the tubes in inches. (b) No tube shall be less than 12 S.W.G.(.104") thick. |
Earlier text: the 2008 DIPP web edition
HEADERS AND SECTION BOXES OF WATER TUBE BOILERS
Brass and Copper Tubes
The thickness of tapered brass and copper smoke tubes for locomotive boilers shall, in the case of tubes of an external diameter of 1-1/2 to 1-7/8 inches inclusive, be not less than 12 S.W.G. (.104inch) at the smoke-box end and10 S.W.G.(.128 inch) at the other end in the case of tubes of an external diameter of 2 to 2-3/8 inches inclusive, the thickness, at the smoke-box end shall not be less than 11 S.W.G. (.116 inch) and at the other end not less than 9 S.W.G. (.144 inch).