Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 210 — Parts to be stayed
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 211, 212. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 210, Reg. 211, Reg. 212 TUBE PLATES Parts to be stayed
Reg. 211 TUBE PLATES Minimum thickness and cross-section To provide a secure attachment for plain tubes in the tube plates the thickness and cross-section of the plate between the tube holes shall be not less than :- Steel tube plate .125D + .2 = minimum thickness in inches Eqn.(47) .17 + .025 = minimum cross section in square inches Eqn.(48) Copper tube plate, .2D + .4 = minimum thickness in inches Eqn.(49) .527D - .263 = minimum cross section in square inches Eqn.(50) D is the diameter in inches of the tube at the part of attachment to tube plate. Where the thickness and cross-section of the tube plates are less than the minimum the appropriate co-efficient in Eqn.(51) shall be reduced in proportion to the deficit. Reg. 212 TUBE PLATES Holding power of plain tubes
|
Earlier text: the 2008 DIPP web edition
TUBE PLATES
Parts to be stayed
a)The stiffness of tube plates and pitch of stays within the nests of tubes where stay tubes are required and where marginal stay tubes are required in support of blank spaces adjacent to or between the nests shall be determined by flat plate rules under Regulation 195.
b)Tubes plates within the nests of tubes whether fitted with stay tubes or not shall comply with the requirements of Regulation 211 in regard to thickness and cross section between tubes.