Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 194 — Flat plates supported by stays and nuts and large washers or strips or doublings
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 194 FLAT PLATES Flat plates supported by stays and nuts and large washers or strips or doublings
|
Earlier text: the 2008 DIPP web edition
FLAT PLATES
Flat plates supported by stays and nuts and large washers or strips or doublings
a)Where the plates are supported by stays passing through them and are fitted with nuts inside and washers and nuts outside, the diameter of the washers being at least 3 ½ times that of the stay and their thickness at least two-thirds, that of the plate, but not greater than that of the plate, the maximum working pressure shall be : -
100
W. P. = [ ( t - 1 )² + .15 t1² ] Eqn.(29)
A² + B²
b)where the washers have a diameter of at least two-thirds of the pitch of the stays and a thickness of at least two-thirds of the thickness of the plate, but not greater that that of the plate, and are riveted to the plate in an efficient manner, the, maximum working pressure shall be : -
100
W. P. = [ ( t – 1 )² + .35 t1² ] Eqn.(30)
A² + B²
c)Where the plate is stiffened by strips at least two thirds of the pitch of the stays in breadth which have a thickness of at least two-thirds of that of the plate but not greater than that of the plate, and are riveted to the plate in an efficient manner, the maximum working pressure shall be : -
100
W. P. = [ ( t - 1 )² + .55 t1² ] Eqn.(31)
A² + B²
d)Where the plates are fitted with doubling plates having a thickness of at least two-thirds of that of the plate but not greater that that of the plate, and are riveted to them in an efficient manner, the maximum working pressure shall be : -
100
W. P. = [ ( t - 1 )² + .85 t1² ) ] Eqn.(32)
A² + B²