BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)

Regulation 189 — Dished ends subject to internal pressure

Unofficial DPIIT web edition · not verified0 amendments found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette
Reg. 189
DISHES END PLATES


Dished ends subject to internal pressure

a) For unstayed ends of steam and water drums, tops of vertical boilers, etc., when dished to partial spherical form the maximum working pressure shall be determined by the following formula : -
W.P. = 15 x S x (t - 1) Eqn.(24)
R

Where
W.P. is the working pressure in lbs. per square inch,

t is the thickness of end plates in 32nds of an inch.

R is the inner radius of curvature of the end in inches, which shall not exceed the external diameter of the shell to which it is attached,

S is the minimum tensile breaking strength of plate in tons per square inch, or whatever is allowed for it.
b) The inside radius of curvature of the flange shall be not less than 4 times the thickness of the end plate, and in no case less that 2-1/2 inches.
c) When the end has a manhole in it (t - 5), shall be substituted for (t - 1) in the formula.
d) The total depth of flange of manhole from the outer surface in inches measured on the minor axis shall be at least equal to -
(T x W) 1/2 = depth of flange in inches. Eqn.(25)

where
T is the thickness of the plate in inches,, and

W is the minor axis of the hole in inches.

NOTE - The foregoing provisions shall not preclude the use of dished ends in compliance with Regs.275 to 278, where not fitted with an up-take.
Earlier text: the 2008 DIPP web edition

DISHES END PLATES

Dished ends subject to internal pressure

a)For unstayed ends of steam and water drums, tops of vertical boilers, etc., when dished to partial spherical form the maximum working pressure shall be determined by the following formula : -

                             15 x S x (t - 1)
W.P. =                                                  Eqn.(24)
                                   R

Where

W.P. is the working pressure in lbs. per square inch,

t is the thickness of end plates in 32nds of an inch.

R is the inner radius of curvature of the end in inches, which shall not exceed the external diameter of the shell to which it is attached,

S is the minimum tensile breaking strength of plate in tons per square inch, or whatever is allowed for it.

b)The inside radius of curvature of the flange shall be not less than 4 times the thickness of the end plate, and in no case less that 2-1/2 inches.

c)When the end has a manhole in it (t - 5), shall be substituted for (t - 1) in the formula.

d)The total depth of flange of manhole from the outer surface in inches measured on the minor axis shall be at least equal to -

(T x W) ¹ᐟ² = depth of flange in inches.      Eqn.(25)

where

T is the thickness of the plate in inches,, and

W is the minor axis of the hole in inches.

NOTE - The foregoing provisions shall not preclude the use of dished ends in compliance with Regs.275 to 278, where not fitted with an up-take.