Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 183 — Maximum Pitch of Rivets in longitudinal joints
Unofficial DPIIT web edition · not verified0 amendments found
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette
| Reg. 183 SHELLS Maximum Pitch of Rivets in longitudinal joints The maximum pitch of the rivets in the longitudinal joints of boiler shells shall be :-
Where T = the thickness of the shell plate in inches. C is a co-efficient as given in the following table : -
|
Earlier text: the 2008 DIPP web edition
SHELLS
Maximum Pitch of Rivets in longitudinal joints
The maximum pitch of the rivets in the longitudinal joints of boiler shells shall be :-
C x T + 1.625 = maximum pitch in inches Eqn. (11)
Where
T = the thickness of the shell plate in inches.
C is a co-efficient as given in the following table : -
Co-efficient for
Number of Rivets Per Co -efficient for Lap Co-efficient for single
double Butt-strapped
pitch joints Butt- strapped Joints
joints
1 1.31 1.53 1.75
2 2.62 3.06 3.50
3 3.47 4.05 4.63
4 4.14 - 5.52
5 - - 6.00