BETAIndependent engineering reference. Source-text verification is ongoing.Verification ongoing.Verification status →
IBRsourceIndian Boiler Regulations, made clear

Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)

Regulation 166 — Doors and Cross Bars

Unofficial DPIIT web edition · not verified3 amendments found

Text in the DPIIT web edition

Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.

Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette
Reg. 166
MANHOLES, MUDHOLES, ETC.
Doors and Cross Bars

a) All internally fitted doors of manholes, mudholes and sightholes shall be of wrought steel built up or pressed to shape and annealed or made from one thickness of plate with a machined recess for the jointing material or may be a steel casting. Their spigot part or the recess shall not have a greater clearance than 1/16th inch all round i.e. the axis shall not be less than 1/8th inch smaller than the holes in which they are fitted.
b) The studs or bolts of large doors may be screwed through the plates and riveted over when the working pressure of the boilers does not exceed 200 lbs. per square inch. When such pressure exceeds 200 lbs. per square inch, the studs or bolts need not be screwed through the full thickness of the plate, provided that the depth of screwing is not less than the diameter of the stud and the stud is locked against turning by welding or other means approved by the Inspecting Authority. Lugs may be satisfactorily welded to manhole doors for the attachment of bolts. All welds shall be made to the satisfaction of the Inspecting Authority.
c) Internal doors for opening not larger than 9 inches x 7 inches size need only be fitted with one stud, which shall be provided with an integral colar and screwed through the plate with a nut on the inside of the door. Internal doors of opening not larger than 5 inches x 3½ inches may have the stud forged solid with the door or screwed, be efficiently riveted to the doors. Where the door of a mudhole cleaning hole or sight hole is fabricated by welding for boilers not exceeding a working pressure of 8.8 kg./cm.2 (125 lbs. per sq. inch), the stud shall pass through the plate and be secured to it by strength-welding on the inside and fillet-welding on the outside to the satisfaction of the Inspecting Authority. The door shall be stress relieved by heat-treatment after welding.
d) The cross bars shall be of substantial proportions and of mild or wrought steel.
Earlier text: the 2008 DIPP web edition

MANHOLES, MUDHOLES, ETC.

GENERAL

Doors and Cross Bars

a)All internally fitted doors of manholes, mudholes and sightholes shall be of wrought steel built up or pressed to shape and annealed or made from one thickness of plate with a machined recess for the jointing material or may be a steel casting. Their spigot part or the recess shall not have a greater clearance than 1/16th inch all round i.e. the axis shall not be less than 1/8th inch smaller than the holes in which they are fitted.

b)The studs or bolts of large doors may be screwed through the plates and riveted over when the working pressure of the boilers does not exceed 200 lbs. per square inch. When such pressure exceeds 200 lbs. per square inch, the studs or bolts need not be screwed through the full thickness of the plate, provided that the depth of screwing is not less than the diameter of the stud and the stud is locked against turning by welding or other means approved by the Inspecting Authority. Lugs may be satisfactorily welded to manhole doors for the attachment of bolts. All welds shall be made to the satisfaction of the Inspecting Authority.

c)Internal doors for opening not larger than 9 inches x 7 inches size need only be fitted with one stud, which shall be provided with an integral colar and screwed through the plate with a nut on the inside of the door. Internal doors of opening not larger than 5 inches x 3½ inches may have the stud forged solid with the door or screwed, be efficiently riveted to the doors. Where the door of a mudhole cleaning hole or sight hole is fabricated by welding for boilers not exceeding a working pressure of 8.8 kg./cm.2 (125 lbs. per sq. inch), the stud shall pass through the plate and be secured to it by strength-welding on the inside and fillet-welding on the outside to the satisfaction of the Inspecting Authority. The door shall be stress relieved by heat-treatment after welding.

d)The cross bars shall be of substantial proportions and of mild or wrought steel.

Amendments found

Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.

DateNotificationPartActionWhat changed (summary)Web edition
2006-08-07G.S.R. 201SubstitutedReplaces regulation 166 with new provisions on internal doors.listed before the capture
2008-06-27G.S.R. 123 OCR of scanAmendedReplaces the thickness formulae for circular and elliptical internal doors.
Uncertain: Formula text is badly garbled in OCR.
listed before the capture
2015-04-15G.S.R. 286(E)(f)AmendedRedefines f as the maximum permissible stress from the governing code of the material.listed before the capture