Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 162 — Mountings on Flat Plates
Unofficial DPIIT web edition · not verified0 amendments found
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine); the same page also prints regulations 161, 163. The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
Unofficial DPIIT web edition · archived 2022 · not checked against the Gazette
| Reg. 161, Reg. 162, Reg. 163 STAND PIPES, PADS ETC. Attachment of Water and Pressure Gauges Water gauge and pressure gauge siphons may be attached direct to the front end plates without the intervention of a pad or stand pipe, provided they are flanged and secured by studs. If the studs are screwed through the plate, nuts shall be fitted on the inside of the plate. Reg. 162 STAND PIPES, PADS ETC. Mountings on Flat Plates Where the flanged mountings are attached direct to a flat plate, such mountings shall be provided with a substantial spigot the full thickness of the boiler plate. Reg. 163 STAND PIPES, PADS ETC. Bolts and Nuts Bolts and nuts shall be machined where they come in contact with the flanges, and all holes in saddles and pads shall be drilled. NOTE – In all cases where boiler is lagged the joint of the mountings shall be clear of the lagging surface or the lagging kept clear of flange so that the joint can be inspected and, when necessary, remade. |
Earlier text: the 2008 DIPP web edition
STAND PIPES, PADS ETC.
GENERAL
Mountings on Flat Plates
Where the flanged mountings are attached direct to a flat plate, such mountings shall be provided with a substantial spigot the full thickness of the boiler plate.