Indian Boiler Regulations, 1950 (superseded 1 Oct 2026)
Regulation 148 — Stay Tubes
Text in the DPIIT web edition
Archived copy captured 03 Aug 2022 (Wayback Machine). The text matches the 2019 capture; amendments from 2020 onwards are probably not included. Units as printed.
| Reg. 148 STAY TUBES Stay Tubes
TABLE
|
Earlier text: the 2008 DIPP web edition
STAY TUBES
GENERAL
Stay Tubes
a)Stay tubes are tubes having a weld depth equal to the nominal tubes thickness plus 3 millimetres. These stay tubes are not required within tube nests except when the tube nests comprise tubes which are expanded only.
b)If tube nests comprise plain tubes that are expanded and beaded, expanded and belled or expanded and welded, welded stay tubes shall be used in flat plate loadings outside the tube area.
c)For plain tubes or stay tubes exposed to flame or gas temperatures exceeding 600°C, the ends of welded tubes shall be dressed flush with the welds. If not so exposed, the ends of welded tubes shall extend a maximum of 10 millimetres beyond the weld or, in the case of expanded tubes the tubes shall project beyond the tube plate upto a maximum of 15 millimetres.
d)Each stay tube shall be designed to carry its due proportion of the load on the plates which it supports.
e)The thickness of stay tubes welded into tube plates shall be such that the axial stress on the thinnest part of the tube does not exceed 70 N/mm2.
f)The thickness of stay tube at any part shall not be less than the values shown in the Table below. Minus tolerances shall be taken into account when ordering tubes.
Nominal outside diameter in millimetres Minimum thickness in millimetres Not exceeding 38 2.28 Exceeding 38 but not exceeding 51 2.81 Exceeding 51 but not exceeding 70 3.12 Exceeding 70 but not exceeding 76.2 3.38 Exceeding 76.2 but not exceeding 88.9 3.96 Exceeding 88.9 but not exceeding 101.6 4.26 Exceeding 101.6 but not exceeding 127 4.55
Amendments found
Machine-assisted list from the amending notifications (DPIIT copies; 1990–1998 from scanned Gazette issues on India Code); may be incomplete.
| Date | Notification | Part | Action | What changed (summary) | Web edition |
|---|---|---|---|---|---|
| 1989-05-08 | compilation-1987-1998#p3 OCR of compilation | Substituted | Replaces regulation 148 on minimum thickness of stay tubes, with stress limits for screwed and welded stay tubes. | listed before the capture | |
| 1994-02-07 | G.S.R. 107 OCR of scan | Substituted | Replaces regulation 148 on stay tubes: when required, welding and projection limits, load sharing, 70 N/mm2 axial stress and a minimum thickness table. | listed before the capture |